XGN □ -12 (Z)/T630-20 series 10KV boundary circuit breaker switchgear

product details

Product Overview

When there is an internal fault in the user of the 10 kV cable line T-connection, when the fault occurs in the incoming section, or when the fault occurs inside the user's incoming switch, but the relay protection action time limit does not match the relay protection action time limit of the power supply company's substation outgoing switch, it will cause the substation outgoing switch to trip. If the nature of the fault is permanent and the outgoing switch fails to overlap, an accident of a medium voltage user will cause a power outage of the entire distribution line, which will have a negative impact on society.

Install a user boundary switch (referred to as a watchdog) at the T-junction or end of the user branch line (responsibility boundary point) mentioned above. After judgment, it is confirmed that an accident (overcurrent, short circuit, low current grounding, etc.) has occurred within the user, and the fault is isolated to ensure the restoration of power supply to non faulty users. This can reduce the power outage area and solve the responsibility dispute between users and the power supply bureau.

Usage conditions

Normal conditions:

Maximum ambient temperature:+40 degrees Celsius

Daily maximum average relative humidity: 95%

Daily average temperature:+35 degrees

Maximum average monthly relative humidity: 90%

Minimum temperature: -40 degrees Celsius

Maximum altitude: 4000 meters

Special conditions:

According to the IEC60694 standard, for special operating conditions that are different from normal operation, the manufacturer and end user must agree. If it involves harsh operating environments, it is necessary to consult the manufacturer and supplier.

Model meaning

XGN□-1224系列全绝缘全封闭充气式金属开关设备型号含义

Meaning of XGN □ -1224 series fully insulated and fully enclosed inflatable metal switchgear model

XGN□-1224系列全绝缘全封闭充气式金属开关设备技术参数


Technical parameters of XGN □ -1224 series fully insulated fully enclosed inflatable metal switchgear


Compliant with StandardsCompliant

GB1984 High Voltage AC Circuit Breakers

GB/T11022 Common technical requirements for high-voltage switchgear and control equipment standards

GB3906 AC Metal Enclosed Switchgear and Control Equipment

GB/T726-2000 Basic Test Methods for Relays and Devices

GB/T17626.4-2008 Electromagnetic Compatibility Testing and Measurement Techniques - Electrical Fast Transient Pulse Group Immunity Test

GB1985 High Voltage AC Isolation and Grounding Switches


Basic Structure

Low voltage chamber

It can be equipped with a secondary low-voltage room on the top of the switchgear, which is used for installing control units such as ammeters, relays, and live locks.

Cable room

Configure the labeled cable head. All sleeves have the same height from the ground and are protected by cable compartment covers. This cover plate can be interlocked with the grounding switch. Note: For installation of cable heads, please refer to the Installation Manual for Shielded Cable Splices.

Temperature and humidity controller

Adopting imported high-performance temperature and humidity sensors, it can simultaneously measure and control temperature and humidity signals. Automatically start the heater and adjust the actual temperature and humidity of the tested environment.

Voltage transformer

10kV fully insulated, fully shielded, and touchable voltage transformers can be configured as needed to meet the requirements of distribution network automation. Can be used to provide voltage signals for metering/measurement, and power supply for switch electric operating mechanisms.

Electromagnetic lock (electric 24V/220V)

The cabinet door suitable for indoor high-voltage switchgear needs to be interlocked at the locking position to prevent the occurrence of misoperation.

Current transformer

Each module can be equipped with current transformers, which must be installed inside the cable compartment.

Attention:

If one phase fuse blows, all three-phase fuses must be replaced

XRNP-12KV/0.5A-50KA

XRNP-12KV/0.2A-50KA

The above models of fuses can be selected

Outline dimension drawing

XGN□-12(Z)A型高压交流用户分界开关柜外形图

Outline drawing of XGN □ -12 (Z) A-type high-voltage AC user boundary switchgear

XGN□-12(Z)A型高压交流用户分界开关柜外形图