HXGN □ -12 series AC high-voltage vacuum ring main unit

product details

HXGN □ -12 type box type fixed fully enclosed switchgear is a vacuum load switchgear developed by our company, with a three-phase AC 50Hz and a rated voltage of 12kV. It is referred to as the vacuum ring main unit and is suitable for the ring network power supply of 10kV systems and the power supply and distribution systems of industrial and mining enterprises, high-rise buildings, residential communities, etc. The main switch adopts vacuum arc extinguishing, which has the advantages of strong breaking ability and reliable performance, especially suitable for frequent operating modes.

The vacuum ring main unit cabinet consists of three types of cabinets: vacuum load switch cabinet, vacuum load switch fuse combination electrical cabinet, and vacuum circuit breaker cabinet. Vacuum load switch and vacuum load switch fuse combination electrical appliances both use the principle of vacuum arc extinguishing; The dynamic and static contacts are sealed in the vacuum arc extinguishing chamber. When the vacuum arc is cut off, the metal vapor quickly diffuses and extinguishes the arc when the power supply crosses zero, and the insulation strength recovers much faster than air. Therefore, the breaking performance is good and the work is reliable. The transfer current of the air load switch (gas or compressed air load switch) combination device can generally only reach about 1000A, while the transfer current of the vacuum load switch fuse combination device can reach 3150A (which can be larger), making the operation safer and more reliable.

This product complies with the relevant provisions of IEC298, GB3906, GB3804 and other standards.

Normal usage conditions

Environmental temperature: -35 ℃~45 ℃;

Altitude: ≤ 1000m;

Relative humidity: ≤ 95% (daily average) ≤ 90% (monthly average);

Earthquake intensity: ≤ 8 levels;

Place of use: Indoor, without fire, explosion hazards, severe pollution, chemical corrosion, long-term severe vibration and other environmental factors.

Note: If the above normal operating conditions are exceeded, special written instructions are required when placing an order.


交流高压-2.jpg

Product features

The ring main unit is assembled with 8MF profiles, and the module holes for the full frame installation are E=20mm.

The ring main cabinet is equipped with FZN21-12D or FZN25-12 vacuum load switches or VS1-12 vacuum circuit breakers (side mounted), which are equipped with isolation switches and vacuum negative terminals

Load switch, vacuum circuit breaker, grounding switch, and isolation switch and grounding switch all have obvious fractures.

Isolation switches, vacuum load switches, vacuum circuit breakers, grounding switches, and cabinet doors have complete and reliable mechanical linkage and interlocking devices, which can effectively prevent misoperation and ensure

Ensure safety maintenance. Can be operated manually or electrically.

The cabinet door and instrument door of the measuring cabinet are equipped with lead seal pins.

The fuse combination electrical cabinet and fuse tube are equipped with firing pins. In the case of a short circuit, the firing pin impacts the tripping mechanism, achieving rapid disconnection and effectively protecting electrical equipment.

The ring main unit adopts front operation and reliable wall installation.

Power supply operation: Only when the cabinet door is closed and locked, and the grounding switch is operated to the "open" position, can the load switch be operated to the closed position.

Power outage operation: Only when the load switch is in the isolated position can the grounding switch be closed. When the grounding switch is in the closed position, insert the insulation partition in place to open the cabinet

Door. The vacuum arc extinguishing chamber is reliably interlocked with the isolation knife, while the isolation knife and the grounding knife are interconnected and interlocked with the cabinet door. The insulation partition is also interlocked with the cabinet door.